Welcome to wins!

GCS low voltage withdrawable switch cabinet

Short Description:

ProductCategory: Low Voltage Switchgear Series

Intro: GCS type low voltage withdrawable switchgear is suitable for power distribution systems in power plants, petroleum, chemical, metallurgy, textile, high-rise buildings and other industries. In large-scale power plants, petrochemical systems and other places with a high degree of automation and computer interfaces, it is used as a three-phase AC frequency of 50 (60) Hz, rated working voltage of 400V, 660V, and rated current of 5000A and below. Low-voltage complete set of power distribution equipment used in power distribution, centralized motor control, and reactive power compensation.


Product Detail

Product Tags

Technical parameters

Name

Parameters

rated voltage (V) for main circuit

Communication 400/660

 Auxiliary circuit rated voltage

AC 220,380(400), DC 110,220

rated frequency (Hz)

50(60)

rated insulation voltage (V)

660

Current rating (A)

Horizontal busbar

w 5000

rated current (A)(MCC)

Vertical busbar

1000

Bus rated short-time withstand current (kA/1s)

50,80

Bus rated peak tolerance current (kA/0.1s)

105,176

Power frequency test voltage (V/min)

Main circuit

2500

Auxiliary circuit

2000

Bus bus

Three-phase four-wire system

A.B.C .PEN

Three-phase five-wire system

A.B.C .P E.N

Protection level

 

IP30. IP40

GCS Use environmental conditions

♦ The ambient air temperature is not higher than +40℃, not lower than -5℃, and the average temperature within 24 hours must not be higher than +35℃. When it exceeds, it needs to be derated according to the actual situation;

♦ For indoor use, the altitude of the place of use must not exceed 2000m;

♦ The relative humidity of the surrounding air does not exceed 50% when the maximum temperature is +40°C, and a larger relative humidity is allowed at lower temperatures, such as 90% at +20°C. It should be considered that accidents may occur due to temperature changes The effect of condensation;

♦ When the device is installed, the inclination from the vertical plane does not exceed 5°, and the entire group of cabinet rows is relatively flat (in line with GBJ232-82 standard);

♦ The device should be installed in a place where there is no severe vibration and shock, and it is not enough to subject the electrical components to no corrosion;

♦ When the user has special requirements, he can negotiate with the manufacturer to solve it.